Function Prog.
no.
Level
1)
Standard value
With prim contr/system pump
No | Yes
1930 E Yes
Swimming pool circuit
Flow temp setp cons request 1959 C 70°C
DHW charging priority
No |Yes
1974 E Yes
Excess heat draw
Off | On
1975 E ON
With buffer
No |Yes
1978 E Yes
With prim contr/system pump
No |Yes
1980 E Yes
Swimming pool
Setpoint solar heating 2055 Eu 26°C
Setpoint source heating 2056 Eu 22°C
Charging priority solar
Priority 1 | Priority 2 | Priority 3
2065 E Priority 3:
Swimming pool temp max 2070 E 32°C
With solar integration
No | Yes
2080 E Yes
Primary contr/system pump
Flow temp setpoint min 2110 E 8°C
Flow temp setpoint max 2111 E 80°C
Syst pump on heat gen lock
Off | On
2121 E Off
Mixing valve boost 2130 E 0°C
Actuator running time 2134 E 120 s
Boiler
Release below outside temp 2203 E --- °C
Full charging buffer
Off | On
2208 E Off
Setpoint min 2210 E 20°C
Setpoint max 2212 E 88°C
Setpoint manual control 2214 Eu 60°C
Burner running time min 2241 E 1 min.
Burner off time min 2243 E 7 min.
SD burner off time 2245 E 20°C
Pump overrun time 2250 E 2 min.
Pump overr time after DHW 2253 E 1 min.
Frost prot plant boiler pump
Off | On
2300 E Off
Boiler pump on heat gen lock
Off | On
2301 E Off
Impact heat generation lock
Heating mode only | Heating and DHW mode
2305 E Heating mode only
Programming
7308272-03 03.14 Paramount three 30-115 kW 59