Function Prog.
no.
Level
1)
Standard value
Max fan output heating full charging 2442 E Paramount Three 30: 28
kW
*)
Paramount Three 40: 38
kW
*)
Paramount Three 60: 50
kW
*)
Paramount Three 80: 70
kW
*)
Paramount Three 95: 90
kW
*)
Paramount Three 115:
110 kW
*)
Fan output DHW max. 2444 E Paramount Three 30: 28
kW
*)
Paramount Three 40: 38
kW
*)
Paramount Three 60: 50
kW
*)
Paramount Three 80: 70
kW
*)
Paramount Three 95: 90
kW
*)
Paramount Three 115:
110 kW
*)
Fan shutdown heating mode
Off | On
2445 E Off
Fan shutdown delay 2446 E 3 s
Controller delay
Off | Heating mode only | DHW mode only | Heating and DHW mode
2450 E Heating mode only
Fan output controller delay 2452 E Paramount Three 30: 10,0
kW
*)
Paramount Three 40: 14,0
kW
*)
Paramount Three 60: 21
kW
*)
Paramount Three 80: 29
kW
*)
Paramount Three 95: 36
kW
*)
Paramount Three 115: 40
kW
*)
Controller delay duration 2453 E 40 s
Switching diff on HCs 2454 E 4°C
Switching diff off min HCs 2455 E 5°C
Switching diff off max HCs 2456 E 10 °C
Switching diff on DHW 2460 E 5°C
Switching diff off min DHW 2461 E 6°C
Switching diff off max DHW 2462 E 8°C
Delay heat request special op 2470 E 0 s
Programming
7308272-03 03.14 Paramount three 30-115 kW 61