Fig. 15: Room temp limitation
sRE159A
TRx
TRw
SDR
P
t
Room temperature actual value
Room temperature setpoint
Room switching difference
Pump
Time
Boost heating
(770, 1070, 1370)
The boost heating is active if the room set point is switched from protection
mode or reduced mode to comfort mode. During the boost heating the the room
set point is increased to the value set here. This causes the actual room tempera-
ture to increase to the new set point within a short period of time. The boost
heating is ended if the room temperature measured with a RGT/RGTF or RGB
2)
room unit increases to 0.25 °C below the comfort set point.
Without room sensor or without room influence the boost heating is carried out
based on an internal calculation. Due to the room set point acting as a basis, the
effect of the duration of the boost heating and that of the flow temperature
works differently for each outside temperature.
Fig. 16: Boost heating
TRSPR
TRw
TRx
DTRSA
Room temperature setpoint
Room temperature actual value
Room temperature set point-raised
2 )
accessories
Programming
7308272-03 03.14 Paramount three 30-115 kW 83