Programming
42 POTTERTON COMMERCIAL
120-393 632.4 04.08 Fh
Legionella funct periodically
1641 F
3
Legionella funct weekday
Monday | Tuesday | Wednesday | Thursday | Friday |
Saturday | Sunday
1642 F
Sunday
Legionella funct time
1644 F
- - : - -
Legionella funct setpoint
1645 F
65°C
Legionella funct duration
1646 F
- - -
Circulating pump release
Time programme 3/HKP | Drinking water release |
Time programme 4/TWW
1660 I
Drinking water
release
Circulation pump cycle operation
OFF | ON
1661 I
ON
Boiler
Nominal value manual operation
2214 E
60°C
Drinking water sto-
rage
Parameter according to hydraulic diagram!
Flow setpoint boost
5020 F
18°C
Configuration
Hydraulic scheme
5701 I
2
Heating circuit 1
OFF | ON
5710 I
ON
Heating circuit 2
OFF | ON
5715 I
ON
Zones with feed pump
No |Yes
5761 I
No
HK1with feed pump
No |Yes
No
HK2 with feed pump
No |Yes
No
TWW with feed pump
No |Yes
No
Relay output K2
Default | Message output | Alarm output | operation
message | External transformer | Heating circuit
pump HK2 | Circulation pump | Gate veil function |
Pump hydraulic bypass | Feed pump Q8 | Basic func-
tion K2 | TWW-charging | Threshold analoguous sig-
nal RelCl | Exhaust gas flap | Collector pump | Fan
switch-off | Pump Q1 | DHW mixing pump Q35
5920 I
Fan switch-off
Feed pump
Relay output 1 RelCl
Default | Message output | Alarm output | Operation
message | External transformer | Heating circuit
pump HK2 | Circulation pump | Gate veil function |
Pump hydraulic bypass | Feed pump Q8 | Basic func-
tion K2 | TWW-charging | Threshold analoguous sig-
nal RelCl | Exhaust gas flap | Collector pump | Fan
switch-off | Pump Q1 | DHW mixing pump Q35
5922 I
Default
Relay output 2 RelCl
Default | Message output | Alarm output | Operation
message | External transformer | Heating circuit
pump HK2 | Circulation pump | Gate veil function |
Pump hydraulic bypass | Feed pump Q8 | Basic func-
tion K2 | TWW-charging | Threshold analoguous sig-
nal RelCl | Exhaust gas flap | Collector pump | Fan
switch-off | Pump Q1 | DHW mixing pump Q35
5923 I
Default
Function
Prog.
-No.
Set-
ting
level
1
Standard value
Modi-
fied
value

Table of Contents