POWER ELECTRONICS
SD300 PROFINET
PARAMETERS CONFIGURATION
27
Code
Parameter Name
Value
Description
Pr
12 Lost Cmd
Source
0 None
Select the drive operation mode for a “Lost
Command” condition caused by a communication
error.
The following table lists the available operation
modes:
OPT.
DESCR.
DESCRIPTION
0
None
Speed reference becomes
the operating frequency
without a protective
operation.
1
Free-Run
The drive cuts off the
output and the motor free-
runs.
2
Dec
The drive performs a
deceleration stop
according to the time set at
“Trip Dec Time”.
3
Hold Input
The drive keeps operating
using the speed reference
received before the
command loss.
4
Hold Output
The drive keeps operating
using the operation
frequency before the
command loss.
5
Lost Preset
The drive operates using
the frequency reference
set at Pr-14 “Lost Preset
F.
13 Lost Cmd Time
1.0
Sets the drive time taken to decide that a
command has been lost, and apply the “Lost
Command Modes” set at [Pr-12]. The setting
range is: 0.1 120 [s]
14 Lost Preset F
0.00
Sets a protective function that allows the drive to
run at a frequency reference pre-set at [Pr-14]
when command via the communication module
is lost. The setting range is between the start
frequency and the maximum frequency [Hz].