EasyManua.ls Logo

Power Electronics SD 300 Series - Setpoint Value; Current Speed Value; Alarm Information

Power Electronics SD 300 Series
55 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SD300 PROFINET
POWER ELECTRONICS
36
SUPPORTED PROFIDRIVE CYCLIC TELEGRAM
Setpoint Value
It is the frequency reference for drive operation. The Setpoint Value is
expressed in Hz and can be increased or decreased by 0.01 Hz.
Current Speed Value
It represents the drive current output frequency. The Current Speed Value
is expressed in Hz and can be increased or decreased by 0.01 Hz.
Alarm Information
Bit
Name
Description
0
Bit for displaying “latch type
trip information-1”
This bit is set to 1 when more than one bit in the
“latch type trip information-1parameter bit field is
set to 1. Otherwise, it is set to 0. This bit references
address 0h0330 in the drive compatible parameter
communication addresses
1
Bit for displaying “latch type
trip information-2”
This bit is set to 1 when more than one bit in the
“latch type trip information-2parameter bit field is
set to 1. Otherwise, it is set to 0. This bit references
address 0h0331 in the drive compatible parameter
communication addresses.
2
Bit for displaying “level type
trip information”
This bit is set to 1 when more than one bit in the
“level type trip information” parameter bit field is set
to 1. Otherwise, it is set to 0.
This bit references address 0h0332 in the drive
compatible parameter communication addresses.
3
Bit for displaying “H/W
Diagnosis Trip information”
This bit is set to 1 when more than one bit in the “H/W
Diagnosis Trip information” parameter bit field is set
to 1. Otherwise, it is set to 0.
This bit references address 0h0333 in the drive
compatible parameter communication addresses.
4
Bit for displaying “Warning
information”
This bit is set to 1 when more than one bit in the
“Warning information” parameter bit field is set to 1.
Otherwise, it is set to 0.
This bit references address 0h0334 in the drive
compatible parameter communication addresses.
5 to 15
-
Reserved.