SUPPORTED PROFIDRIVE CYCLIC TELEGRAM
Ready for operation (Operation by a
PLC is available).
NOT Ready for operation (Operation
by a PLC is not available).
OFF2 (Coast Stop) feature is disabled.
Current operation is maintained.
Stops the motor using a free-run stop
(emergency stop).
OFF3 (Quick Stop) feature is disabled.
Current operation is maintained.
Stops the motor using the setting at
SD300 drive (Ad.8 “Stop Mode”).
Operates the motor using the Setpoint
value (frequency reference received
from a PLC via the Profinet network
communication.
Stops the motor using the setting at
SD300 drive (Ad.8 “Stop Mode”).
Performs acceleration and
deceleration based on the
acceleration and deceleration time
settings at SD300 drive (PAR->DRV)
to reach the Setpoint (frequency
reference).
Forces the operation frequency to “0”.
(Operating frequency drops to “0” after
decelerating based on the Dec Time
set at the drive).
A fixed Ramp Generator operation is
not assigned. Acceleration and
deceleration is performed based on
the Acc/Dec times configured in the
drive group (PAR->DRV) parameter
settings to reach the Setpoint
(frequency reference).
Speed reference from the PLC is
ignored and the Ramp Generator
operation is fixed. The motor is
operated via the network
communication by the Profinet, and