SD300 – PROFINET
POWER ELECTRONICS
22
NETWORK CONNECTIONS
4. NETWORK CONNECTIONS
Network Cable Contacts
Pin No.
Signal
Description
Cable color
1
TX+
Data Transmission (+)
White / Yellow
2
TX-
Data Transmission (-)
Yellow
3
RX+
Data Reception (+)
White / Green
4
None
Not used
Blue
5
None
Not used
White / Blue
6
RX-
Data Reception (-)
Green
7
None
Not used
White / Brown
8
None
Not used
Brown
Communication Cable Connector
Notes:
1- Wires connected to pin#1 and pin#2 must be twisted.
2- Wires connected to pin#3 and pin#6 must be twisted.
Network Cable Specification
Profinet network communication requires STP (category 6a, or higher)