POWER ELECTRONICS
SD300 PROFINET
TROUBLE SHOOTING
51
No.
Symptoms
Resolution
5
The communication
module’s IP address
is randomly changed.
A PLC can forcibly change the communication module
IP address based on the PLC settings. Check the PLC
configuration software and see if the IP change by the PLC
is allowed.
Set the PLC software to use the IP address set at the
communication module if you do not want the
communication module IP to be changed.