www.powershield.com.au 13
13: Charger maximum current setting
Parameter 3: Set up the charger maximum current.
1/2/4/6/8: setting the charger maximum current
1/2/4/6/8 in Ampere. (Default: 8A)
Note: the setting is only effective for the UPS with super
charger
14: Charger Boost voltage setting
Parameter 3: Set up the charger boost voltage.
2.25-2.40: setting the charger boost voltage from 2.25
V/cell to 2.40V/cell. (Default: 2.36V/cell)
15: Charger Float voltage setting
Parameter 3: Set up the charger float voltage.
2.20-2.33: setting the charger float voltage from 2.20
V/cell to 2.33V/cell. (Default: 2.28V/cell)