voltage
Output cable does not
well connected;
Output breaker do not
switch on
Make sure the output cable is well
connected;
Switch on the output breaker.
Utility voltage exceeds
UPS input range.
If the UPS operates at
mode, please pay attention to
remaining backup time needed
Battery LED is flashing
but
no charge voltage and
current
Battery breaker does not
switch on, or batteries
are damaged, or battery
is reversely connected.
battery number and
capacity
are not set
correctly.
Switch on the battery breaker. If
batteries are damaged, need
Connect the battery cables
correctly;
Go to LCD setting of the
number and capacity, set the
The UPS output is in
short circuit
Make sure the load is not in short
circuit, then restart the UPS.
The UPS only works on
bypass mode
Set the UPS working mode to
to reset the times of tra
nsferring to
bypass or re-start the UPS
properly closed;
Battery fuse is no
open;
Or Battery low;
Battery q
wrong;
Power breaker in th
Close the battery switch;
Change the fuse;
Recharge the battery;
Power ON the UPS with AC to set
the battery quantity
&quantity;
Switch
on the power breaker.
continuously and LCD
indicates 1,3,5,9,15, etc
fault codes
Consult with your local agent for
repair