13
ELECTRICAL CONNECTIONS
Refer connection diagram shown on the left side of the enclosure. The diagram shows the terminals viewed from the REAR
SIDE with the controller label upright.
Figure 7.1
TEMPERATURE SENSOR INPUT
Connect 3-wire RTD Pt100 sensor or Thermocouple as shown below.
Figure 7.2
3
2
1
RTD
RTD Pt100, 3-wire
Connect single leaded end of RTD bulb to terminal 1 and the double leaded ends to terminals 2 and 3 (interchangeable) as
shown in Figure 7.2. Use low resistance copper conductor leads of the same gauge and length. Avoid joints in the cable.
Section 7
User Manual
Clave
48 X 48 96 X 96
OUTPUT-1 (Heater Control Output)
The Output-1 is factory configured as SSR Drive. Connect (+) and (-) terminals of SSR to terminals
11 & 10, respectively. Use Zero-Crossover, 3 to 30 VDC operated SSR. Refer Figure 7.3.
Figure 7.3
11
10
RELAY
OUTPUT 3
OUTPUT 1
OUTPUT 2
NO
C NC
NO
CNC
RELAY
SSR
Pt100
INPUT
SSR
RS 485
1
2
3
4
5
6
7
8
9
10
11
12
13
14
1516
17
18
85 ~ 265 V
AC SUPPLY
L
N
48X48
SSR
1
2
3
4
5
13
7
12
8
14
9
15
16
17
11
18
10
6
NL
96X96
RELAY
SSR
OUTPUT1
OUTPUT2
RS485
85~265
VAC
Pt100
INPUT
OUTPUT3
NCNO C
RELAY
NC NOC