PR 9113 - Signal Input;Output Specifications; Current Input;Output Details; 2-Wire Output Specifications

Default Icon
65 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12 9113 - Product Version 9113-004
Coldjunctioncompensation(CJC):
via external sensor in connector 5910 . 20...28°C ±1°C
-20...20°C and 28...70°C ±2°C
viainternalCJCsensor.................................. ±(2.0°C + 0.4°C * t)
t=internaltemperature-ambienttemperature
Sensor error detection ........................................... Programmable ON or OFF
(only wire breakage)
Sensor error current:
when detecting ............................................... Nom. 2 μA
else ....................................................................... 0 μA
Current input:
Measurement range ................................................ 0...20 mA
Programmable measurement ranges ............... 0...20 and 4...20 mA
Input resistance........................................................ Nom. 20 Ω + PTC 50 Ω
Sensor error detection ........................................... Programmable ON / OFF
Only 4...20 mA (NAMUR)
Current output:
Signal range (span) ................................................. 0...20 mA
Programmable signal ranges ............................... 0...20 / 4...20 /
20...0 and 20...4 mA
Load (max.) ................................................................. 20 mA / 600 Ω / 12 VDC
Load stability ............................................................. 0.01% of span / 100 Ω
Sensor error detection ........................................... 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale / Downscale ................. 23 mA / 3.5 mA
Output limitation:
on 4...20 and 20...4 mA signals ................ 3.8...20.5 mA
on 0...20 and 20...0 mA signals .............. 0...20.5 mA
Current limit ............................................................... 28 mA
2-wire 4...20 mA output:
Signal range ............................................................... 4...20 mA
Load stability ............................................................. 0.01% of span / 100 Ω
Load resistance......................................................... (V
supply
-3.5) / 0.023 A [Ω]
External 2-wire supply range ............................. 3.5...26 VDC
Effect of external 2-wire supply
voltage variation ...................................................... < 0.005% of span / V
Status relay in safe area:
Max. voltage .............................................................. 125 VAC / 110 VDC
Max. current ............................................................... 0.5 AAC / 0.3 ADC
Max. AC power .......................................................... 62.5 VA / 32 W
of span =ofthecurrentlyselectedmeasurementrange