SolutionPossible cause
Ensure that the pump switch is set to Automatic.The pump switch is off.
Priva Partner: reset the motor protection in the cabinet.The motor protection has been triggered.
Check which alarm is involved and take action
accordingly.
An alarm has been activated.
Priva Partner: determine what is defective and replace
the defective components.
There is a defect in the circuit that controls the pump
motor.
The system pump runs dry
SolutionPossible cause
NutriJet Inline: the system pump has not been properly
bled or there is no supply water.
NutriJet Bypass: the external pump in the main line is
switched off.
• Priva Partner: check that the pump has not been
damaged by running dry.
• NutriJet Inline: Bleed the system pump and check
if there is sufficient supply water.
• NutriJet Bypass: Check the external pump and
switch it on if it is switched off.
No water is entering the unit
SolutionPossible cause
NutriJet Inline: the system pump has not been properly
bled or there is no supply water.
NutriJet Bypass: the external pump in the main line is
switched off.
• Priva Partner: check the valves before and after the
unit (if fitted).
• Ensure that the filter in the supply line is clean.
• NutriJet Inline: Bleed the system pump and check
if there is sufficient supply water.
• NutriJet Bypass: Check the external pump and
switch it on if it is switched off.
NutriJet Bypass: EC control is unstable
SolutionPossible cause
Priva Partner: ensure a turbulent flow in the main line
by:
The supply water does not mix well with the water in
the main line.
• placing injection tubes in the inlet and outlet of the
supply line. This is only possible if the distance
between the connections of the supply line and the
return line in the main line is at least 1.5 m (see
Wateraanvoer installeren (NutriJet));
• installing a static mixer.
NutriJet Bypass: The EC value deviates significantly
After a successful calibration procedure of the EC measurement, the EC value differs significantly
when the water is checked further down the line or at the drippers. See NutriJet Bypass: EC control
is unstable (page 32)
NutriJet Bypass: The pressure on the pressure reducing valves in the incoming line is too
low
The first manometer on the pressure reducing valves in the incoming line indicates too low a pressure.
SolutionPossible cause
Check the external pump in the main line.The pressure in the main line is too low.
NutriJet - user - 00.00232