For information on certifications and standards, such as certified models and
certificates, see the product markings or visit our website:
http://www.pro-face.com/trans/en/manual/1002.html
DANGER
POTENTIAL FOR EXPLOSION
Suitable for use in Class I, Division 2, Groups A, B, C, and D Hazardous
Locations.
Substitution of any component may impair suitability for Class I, Division 2.
Do not disconnect equipment while the circuite is live or unless the area is
known to be free of ignitable gases concentrations.
Always confirm that this product is suitable for use in hazardous locations by
checking that the ANSI/ISA 12.12.01 or CSA C22.2 N°213 certification
appears on the product labeling.
Do not attempt to install, operate, modify, maintain, service, or otherwise alter
this product except as permitted in this manual. Unpermitted actions may
impair the suitability of this product for Class I, Division 2 operation.
To power on or power off this product installed in a Class I, Division 2
hazardous location, you must either:
Use a switch located outside the hazardous environment, or
Use a switch certified for Class I, Division 1 operation inside the hazardous
area.
Do not disconnect equipment unless power has been switched off or the area
is known to be non-hazardous. This applies to all connections including power,
ground, serial, parallel, and network connections.
Never use unshielded/ungrounded cables in hazardous locations.
When enclosed, keep enclosure doors and openings closed at all times to
avoid the accumulation of foreign matter inside the workstation.
Failure to follow these instructions will result in death or serious injury.