80
Holding Register (Analogue Output) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
Lossnay
LGH Series
Auto Ventilation Mode Available
[READ ONLY]
335 40336
0 = Not available
1 = Available
9
Operation Mode of Temperature
Control Unit
[READ ONLY]
336 40337
0 = Not available (not connected)
1 = Available (connected)
Set Temperature on
Temperature Control Unit
[READ ONLY]
337 40338
0 = No set temperature display
1 = RA (Return Air) temperature
2 = SA (Supply Air) temperature
Outdoor Temperature Sensor
[READ ONLY]
338 40339
0 = Not equipped
1 = Equipped
9
Return Air Temperature Sensor
[READ ONLY]
339 40340
0 = Not equipped
1 = Equipped
9
Supply Air Temperature Sensor
[READ ONLY]
340 40341
0 = Not equipped
1 = Equipped
CO2 Level Sensor
[READ ONLY]
341 40342
0 = Not equipped
1 = Equipped