Holding Register (Analogue Output) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
Lossnay
LGH Series
Minimum Cooling Setpoint
[READ ONLY]
326 40327
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.
Maximum Cooling Setpoint
[READ ONLY]
327 40328
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.
Minimum Heating Setpoint
[READ ONLY]
328 40329
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.
Maximum Heating Setpoint
[READ ONLY]
329 40330
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.
Minimum Auto Setpoint
[READ ONLY]
330 40331
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.
Maximum Auto Setpoint
[READ ONLY]
331 40332
Temperature value in ºC multiplied by 10.
0 = 0ºC … 400 = 40ºC
Note: Only available when ‘Set Temperature on
Temperature Control Unit’ value = 1 or 2.
Energy Consumption Data
Available
[READ ONLY]
332 40333
0 = Not available
1 = Available
9
Number of Fan Speeds
[READ ONLY]
333 40334 Values 1 – 4 valid.
9
Bypass Damper Available
[READ ONLY]
334 40335
0 = Not available
1 = Available
9