78
Holding Register (Analogue Output) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
Lossnay
LGH Series
Auto Fan Speed Control
Availability
[READ ONLY]
315 40316
0 = Not available
1 = Available
Night Purge
[READ ONLY]
316 40317
0 = Normal operation
1 = In night purge operation
During night-purge operation:
- Pressing ON/OFF button starts normal operation.
- When pressing the Ventilation button the Lossnay
remains in bypass mode
9
Maintenance Sign
[READ ONLY]
317 40318
0 = Inactive
1 = Active
9
Filter Sign
[READ ONLY]
318 40319
0 = Inactive
1 = Active
9
Actual Ventilation Mode
[READ ONLY]
319 40320
0 = Lossnay ventilation
1 = Bypass ventilation
9
Actual Supply Fan Speed
[READ ONLY]
320 40321
0 = Stop
1 = Speed 1
2 = Speed 2
3 = Speed 3
4 = Speed 4
9
Actual Extract Fan Speed
[READ ONLY]
321 40322
0 = Stop
1 = Speed 1
2 = Speed 2
3 = Speed 3
4 = Speed 4
9
Setpoint 0.5ºC Increments
Availability
[READ ONLY]
322 40323
0 = Not available
1 = Available
Heat/Cool or Cool-Only
[READ ONLY]
323 40324
0 = Heat and Cool
1 = Cool only
Auto Operation Mode Availability
[READ ONLY]
324 40325
0 = Not available
1 = Available
Heat/Cool or Heat-Only
[READ ONLY]
325 40324
0 = Heat and Cool
1 = Heat only