22
Tower UPS
Voltage
Range
Low Line Transfer
85VAC/75VAC/65VAC/55VAC±5% or 160VAC/140VAC/120VAC/110VAC±5%
(Ambient Temp.<35
0
C)
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Comeback
95VAC/85VAC/75VAC/65VAC or 175VAC/155VAC/135VAC/125VAC ± 5 %
(Ambient Temp.<35
0
C)
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
145 VAC ± 5 % or 300 VAC ± 5 %
140 VAC ± 5 % or 290 VAC ± 5 %
≧
0.99 @ nominal voltage (input voltage)
100/110/115/120/127VAC or 200/208/220/230/240VAC
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range (Batt. Mode)
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Overload
Ambient Temp.<35
0
C
105%~110%: UPS shuts down after 10 minutes
at battery mode or transfer to bypass when
the utility is normal
110%~130%: UPS shuts down after 1minute
at battery mode or transfer to bypass when the
utility is normal
>130%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the
≦
≦
6 % THD (non-linear load)
Transfer
Standard
Model
4 hours recover to 90% capacity (Typical)
Long-run
Model*
Charging Voltage
20-90 % RH @ 0- 40°C (non-condensing)
Less than 50dBA @ 1 Meter
Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC
Power management from SNMP manager and web browser
*Long-run model is only available in 200/208/220/230/240VAC systems.
** Derate capacity to 80% of capacity in Frequency converter mode or when the output voltage is adjusted to 100/200/208VAC.
*** Product specifications are subject to change without further notice.