EasyManua.ls Logo

ProMinent S2Ba - Page 37

ProMinent S2Ba
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Dulcodes UV-Desinfektionsanlage
Page 37
ProMinent
®
Wiring diagram
View of cable connectors from front
Float switch cable
for
Universal signal cable (5-core)
for
Metering monitor cable
for
Diaphragm rupture cable
for
External/contact cable (2 core)
for
Contact open -> alarm
-> pump stops with controller type 0
Contact closed -> metering stroke
Blue and black open
-> alarm signal
Brown and black open
-> alarm signal + pump stops
Pause function:
brown and black closed
-> pump metering
brown and black open
-> alarm + pump stopped
External/contact:
white and black closed
-> start contact for pump
(note pause function:
brown and black closed?)
Analogue:
blue, black
-> analogue output 0/4-20 mA
(note pause function:
brown and black closed?)
Auxiliary frequency:
grey and black closed
-> pump metering at pre-set stroking rate
Circuit examples see p. 40
Features of the S2Ca metering pumps
2 blue/alarm
1 black GND
3 brown pause
1 brown / 5 V
2 white/cod
3 blue
4 black/ GND
1 brown / pause
2 white/cod
3 blue / analogue
4 black/ GND
5 grey/auxiliary
2 brown
4 white
2 blue/alarm
1 black/GND

Table of Contents