AN-X4-AB-DHRIO (DH+) Page 29
Accessing Data
Use the following examples to create a connection using DHP-HMI IP aliasing.
Example: PanelView RSLinx Enterprise
Under Communication Setup:
1. Select Ethernet
2. Add a device
3. Select from Ethernet PLC devices a ControlNet PLC-5 similar to your target (not an Ethernet
PLC!)
Example: RSLinx
Use the Ethernet Devices driver in RSLinx.
Add a device at the aliased IP address.
When you create a DDE/OPC topic, uncheck Use Maximum Packet Size (Ethernet) on the Data
Collection tab in the DDE/OPC Topic Configuration