14
User Manual
FD =
Factory
Default
Setting
Step# Description Pg# Range FD
1 Set Clock 15 12A - 12A
2 Set Day of Week 15 Monday - Sunday
3 Backlight 15 On, Off, 6pm-6am Off
4 Night Dimmer 15 On/Off Off
5 Night Dimmer Start Time 15 12A - 12A 8:00PM
6 Night Dimmer Stop Time 15 12A - 12A 6:00AM
7 Current Service Filter Runtime Hours 0-1999 Hours 0
8 Current Service Filter Calendar Days 0-720 Hours 0
9 Set Service Filter Runtime Hours 0-1999 Hours 0
10 Set Service Filter Calendar Days 0-720 Days 0
11 Setpoint Limits On, Off Off
12 Maximum Heat Setpoint Limit 35 - 99 Degrees 74
13 Minimum Cool Setpoint Limit 35 - 99 Degrees 70
14 Cycles Per Hour No Limit, 2, 3, 4, 5, 6 6
15 Compressor Minimum Off Minutes 0, 3, 5 Minutes 5
16 Min. Heat/Cool Setpoint Difference 0 - 6 Degrees 2
17 1st Stage Deadband 1 - 6 Degrees 2
18 2nd Stage Deadband 0 - 10 Degrees 2
19 Minutes Between 1st and 2nd Stage 0 - 60 Minutes 2
20 2nd StageTurnoff Point Deadband, Setpoint Deadband
21 Fan Off Delay 0, 120 Seconds 0
22 F/C Fahrenheit (F), Celsius (C) F
23 Comfort Recovery On, Off Off
24 Dry Contact Polarity Open, Closed Open
25 Dry Contact Use Condensate Pan, Vacation, FDD Vacation
26 ProStat+ Web Portal On, Off On
27 Local API On, Off Off
28 Available Modes Heat, Cool, Heat or Cool, Auto Auto
29 Show Clock On, Off On
Installer
Setup
Steps
(see
Installer
Manual
for more
details)
3 Setup Step Table