Troubleshooting and Maintenance
For thorough connector cleaning, e.g. after touching the open
connector end), perform wet cleaning using pure Isopropanol
in combination with the cleaning paper.
Alternatives:
Quick thorough cleaning of connectors: cartridge cleaning
tools (such as OPTIPOP or CLETOP) or a card cleaner.
Direct cleaning of the sensor plugs or for cleaning adapters:
use a stick cleaner or
the Diamond Ferrule Cleaner 2.5
(Diamond part number BCC
1030609).
Cleaning FIBERSYSTEM 8000 Instrument Housings
Use a dry and very soft cotton tissue to clean the instrument
housing. In the case of heavy dirt, you can moisten the cotton
tissue in water.
Preserving Connectors
Making connections
Before you make any connection ensure that all cables and
connectors are clean. If they are dirty, use the appropriate
cleaning procedure.
Sensor plug caps
Always make sure the dust cap on the E2000 connector tip closes
when the connector is not in use.
Cleaning the Optical Connectors and Adapters
To clean the connector
1.
2.
Unplug the power supply.
The E2000 connector(s) on the FIBERSYSTEM 8000 are
inside the enclosure.
The Protectowire Company, Inc.
FIBERSYSTEM 8000 - Linear Heat
Series
29