OPTIONAL ATT2 MODULE FOR DC POWER AND ENERGY
±600 VDC/300 VAC differential
±1200 VDC/600 VAC differential
Analog Input Channel Ratio
DC: ±0.1% rdg ±0.1% FS
50/60Hz: ±0.15% rdg ±0.15% FS
At 23ºC ±3ºC, 10% – 100% FS, in addition to error in PQube analog channels
Thermal drift of offset voltage
50A to 600A (depending on sensor model)
50A to 3000A (depending on sensor model)
150% to 200% FS (depending on sensor model)
110% to 200% FS (depending on sensor model)
Accuracy at calibration current
0.15% rdg ±0.15% FS typical at DC
±0.3% rdg ±0.3% FS typical at DC
Hysteresis offset voltage error
< ±20 mV (after excursion of ±100% FS current)
< ±30 mV (after excursion of ±100% FS current)
Thermal drift of offset voltage
(AC or DC) PQube POWER screw terminals [23], [31]
24-48VDC ± 20% (polarity independent)
PQube provides more than 150VDC isolation to all other circuits.
Lithium Polymer Battery (replacement batteries available from PSL).
User controlled. 1 to 10 minutes, 3 minute default.
Storage & Discharge Temp.
Estimated 5+ years, depending on operating and environmental conditions.
User-replaceable while PQube is operating (tool required).
Optional PS1 Plug-in Module
100~240VAC ± 10%. 50/60 Hz
Module provides more than 3200VDC isolation to all other circuits
Sum of true instantaneous per-phase power.
Volt-Amps (apparent power)
Sum of per-phase product of RMS voltage and RMS current, taken over the measurement interval.
True power factor—ratio of Watts to Volt-Amps, displacement PF—cosΘ.
VARs (volt-amps reactive)
Budeanu definition or fundamental VARs—user-selectable.
Carbon (CO
2
rate & accumulated)
Based on patent-pending algorithm using watts and user-selected proportions of generator sources,
and user-supplied carbon generation rates for each source.
Measurement method ANSI C84.1.
L-N or L-Nm for delta configurations. Nm defined as measurement neutral, the instantaneous average
L-E voltage. All
L1, L2, L3, N, E currents. Optional user-selected calculated current on one channel for installations with
N-1 current transformers. All voltages scaled up to 10000:1 for current transformers.
Phase-locked, 10-cycles (50 Hz nominal) or 12-cycles (60 Hz nominal). Approximately 5 readings per
second.
Accuracy excluding external CTs
±0.2% typical at unity power factor, nominal voltage, 20% ~ 100% FS current. Better than ±0.25% rdg
±0.25% FS plus error due to phase angle uncertainty (<1.5° typical) for Θfundamental < ±30°, nominal
voltage, 10% ~ 120% FS current. Θfundamental=angle between fundamental voltage and fundamental
current.
Volt-Amps (apparent power)
Better than ±0.25% rdg ±0.25% FS typical (10% ~ 120% FS)