PULSAR
®
HYDRAULIC DIAPHRAGM
METERING PUMPS
Bulletin: IOM-PSR-1500-Rev.G
Installation, Operation &
Maintenance Manual

Table of Contents

Questions and Answers

  • I
    Isaac JonesAug 18, 2025
    Why Pulsafeeder PULSAR 25HL does not start?
    • A
      Alex KennedyAug 18, 2025
      If your Pulsafeeder Water Pump doesn't start, it could be due to several reasons. The coupling might be disconnected, so ensure it is properly connected. There might be an issue with the power source, so check that. A blown fuse or circuit breaker could also be the cause; replace them, addressing any overload. Look for any broken wires and repair them. Verify that the pump is wired correctly by checking the wiring diagram. Finally, check for any blockages in the pipe or line and open the valves.
  • G
    gamblecurtisAug 20, 2025
    What to do if Pulsafeeder PULSAR 25HL Water Pump has no delivery?
    • C
      Charles JacobsAug 21, 2025
      If your Pulsafeeder Water Pump isn't delivering, there are several potential causes. First, ensure the motor is running by checking the power source and wiring diagram. Verify that the supply tank isn't empty and fill it if needed. Check for clogged lines and clean and flush them. Make sure all line valves are open. Inspect the ball check valves for solids holding them open and clean them. Address vapor lock or cavitation by increasing suction pressure. If the prime is lost, reprime the pump and check for leaks. Clean the strainer, replacing the screen if necessary. For an under-primed hydraulic system, refer to Repriming the Pump.
  • D
    dtaylorAug 23, 2025
    What to do if Pulsafeeder PULSAR 25HL delivery is low?
    • B
      brianchandlerAug 23, 2025
      If your Pulsafeeder Water Pump's delivery is low, several factors could be responsible. Check if the motor speed is too low by examining the voltages, frequency, wiring, and terminal connections, and comparing them to the specifications on the nameplate. Also, inspect the check valves for wear or dirt; clean them, and replace them if damaged. Other potential issues include a hydraulic bypass valve operating each stroke, a calibration system error, product viscosity being too high, product cavitating, a worn or damaged piston seal, or a leaking process pressure relief valve.
  • T
    Timothy AllenAug 26, 2025
    Why is Pulsafeeder Water Pump motor overheating?
    • S
      sarahdavisAug 26, 2025
      If your Pulsafeeder Water Pump motor is overheating, it could be due to a few reasons. The pump might be overloaded, so check the operating conditions against the pump design. There could be high or low voltage, so check the power source. Also, a loose wire could be the culprit, so trace and correct it.
  • J
    joshuawilsonAug 28, 2025
    What causes noisy gearing or knocking in Pulsafeeder PULSAR 25HL?
    • M
      Melissa KirbyAug 28, 2025
      Noisy gearing or knocking in your Pulsafeeder Water Pump can stem from several causes. The discharge pressure might be too high, so reduce it. It could also be water hammer, in which case you should install a PULSAtrol. If the hydraulic bypass valve is set too high, readjust it. Note that nondestructive knocking is characteristic of lost motion pumps when the stroke length is at a partial setting.
  • E
    Erin CraigAug 30, 2025
    Why does Pulsafeeder PULSAR 25HL Water Pump delivery gradually drop?
    • S
      Samuel ShortAug 30, 2025
      If the delivery of your Pulsafeeder Water Pump is gradually dropping, it could be due to several reasons. Check valve leakage could be a cause; clean the valves, and replace them if damaged. There might be a leak in the suction line, so locate and correct it. A fouled strainer could also be the problem, so clean or replace the screen. A change in the product could affect delivery, so check the viscosity. Bypass leakage or a worn piston seal can also cause this issue. Lastly, ensure the supply tank vent isn't plugged.
  • A
    Alec ParrishSep 1, 2025
    Why is Pulsafeeder Water Pump piping noisy?
    • L
      Lauren DaltonSep 1, 2025
      Noisy piping in your Pulsafeeder Water Pump system can be caused by several factors. If the pipe size is too small, increase the size of the piping and install a PULSAtrol. If pipe runs are too long, install a PULSAtrol in line. Should surge chambers be flooded, replace the contents with air or inert gas; if a PULSAtrol is installed, replace the diaphragm and recharge. If no surge chambers are used, install a PULSAtrol.
  • A
    Amy CookSep 3, 2025
    What causes erratic delivery in Pulsafeeder PULSAR 25HL?
    • P
      Philip ClaytonSep 3, 2025
      Erratic delivery in your Pulsafeeder Water Pump can be attributed to several factors. There might be a leak in the suction line, so locate and correct it. Product cavitation could also be the cause, so increase suction pressure. Entrapped air or gas in the product might be the issue. Erratic motor speed could also lead to this problem, so check the voltage and frequency. Lastly, fouled check valves can cause erratic delivery, so clean or replace them if necessary.
  • D
    Diana JonesSep 6, 2025
    Why is Pulsafeeder PULSAR 25HL Water Pump delivery higher than rated?
    • A
      angeljonesSep 6, 2025
      If your Pulsafeeder Water Pump's delivery is higher than rated, it could be due to a few reasons. The suction pressure might be higher than the discharge pressure, so install a backpressure valve. If a back pressure valve is set too low, increase the setting. A leaking back pressure valve could also be the cause, so repair, clean, or replace it. Lastly, a calibration error could lead to higher delivery, so review the calculations.
  • J
    Joshua CarterSep 8, 2025
    What to do if Pulsafeeder PULSAR 25HL Water Pump loses hydraulic oil?
    • J
      Jamie PhillipsSep 8, 2025
      If your Pulsafeeder Water Pump is losing hydraulic oil, several issues could be the cause. A ruptured diaphragm could be leaking, so replace it. A leaky seal could also be the source, so replace it as well. Check for cover gasket leaks and replace or retighten them. If the pump head gasket leaks, replace it and tighten the pump head bolts, applying sealing compound. Also, if the pump head is overfilled, remove the excess oil.

Summary

Installation

Suction Pressure Requirements

Specifies minimum suction pressure needed for optimal pump performance and to prevent cavitation.

Discharge Pressure Requirements

Defines conditions to prevent "flow-through" and ensure accurate metering.

Equipment Setup

Lubrication Requirements

Details the two types of oils used and their applications in the pump.

Startup Procedure

Output Adjustment

Explains how to manually adjust the pump's stroke length for flow rate.

Pump Head Priming (Hydraulic System)

Procedures to purge air from the hydraulic system.

Reagent Head Priming (Product System)

Steps to prime the product side of the pump, including suction lift scenarios.

Calibration Procedure

Method for calibrating the pump to achieve accurate flow rates at different settings.

Maintenance

Oil Changes

Recommended intervals and procedures for changing gear and hydraulic oils.

Wet End Removal, Inspection, and Reinstallation

General procedures for disassembling and reassembling the fluid-handling end.

Standard Diaphragm Replacement

Detailed steps for replacing the pump's diaphragm.

Re-Priming the Pump Head

Procedure to re-prime the hydraulic system after maintenance.

Hydraulic Performance Valve (HPV)

Details the function and maintenance of the HPV.

HPV Removal and Replacement (A & B Pump Heads)

Specific steps for removing and reinstalling the HPV in A & B pump head styles.

HPV Removal and Replacement (C & D Pump Heads)

Specific steps for removing and reinstalling the HPV in C & D pump head styles.

Pump Motor

Replacement Parts

Troubleshooting Chart

Diagnosis of Diaphragm Failure

Guide to identifying potential causes of diaphragm failure based on observed symptoms.

Appendix I: Pulsalarm Leak Detection System

Pulsalarm Leak Detection Diaphragm Maintenance

Procedures for removing, inspecting, and reinstalling the leak detection diaphragm.

Appendix II: Piping Calculations

Appendix III: Oil Specifications

Appendix IV: Bolt Torque Requirements

Appendix V: Pulsafeeder Accessories

Pulsafeeder PULSAR 25HL Specifications