Page 19 
DATEM Flags 
 
P064 Near Band 
 
 
This parameter used in conjunction with P65, is designed to prevent the echo 
‘jumping’ to a false echo that is further away when the echo enters into the near 
blanking area. As the echo approaches to within 0.2m from the transducer 
blanking area and is then ‘lost’ it will not jump to any echo that is further than 
0.5m (near jump) away from the blanking. Thus preventing the unit from reading 
a low value when it is submerged and possibly switching off pumps. 
 
P065 Near Jump 
 
 
See above.  
Note. With reference to the above two parameters see P080 Lost Lock 
 
P067 Use First (Software Revisions prior to 3.6.0) 
 
 
This parameter is used to determine which echo is selected for processing. When 
set to zero the echo with  largest valid peak is chosen, when set to 1 the First valid 
echo will be selected unless a larger echo is present beyond the Jump Cut Off 
point (P84). 
N.B. In software versions up to 2.7.2 Jump Cut Off is P83