    Oscar CombsAug 7, 2025
    What to do if my Pulsar Ultra 3 Measuring Instruments display shows an incorrect reading for the current level?
    • S
      sarah27Aug 7, 2025
      If your Pulsar Measuring Instruments display is showing an incorrect reading, measure the actual distance from the transducer head to the surface of the material. Then, enter Program Mode and directly access P21 (Set Distance), type in the measured distance, press ENTER, and ENTER again when prompted. Wait until SET is displayed and return to Run Mode. The display should now update to the correct reading.
  • J
    jacobjohnsonAug 12, 2025
    Why are the LEDs changing color at relay switch points, but the relays aren't changing state on my Pulsar Measuring Instruments?
    • T
      Thomas WadeAug 12, 2025
      If the LEDs on your Pulsar Measuring Instruments are changing color at the relevant relay switch points, but the relays are not changing state, check the power supply to the unit and ensure the voltage selector is set to the correct position.
  • S
    Sean SmithAug 17, 2025
    What to do if my Pulsar Measuring Instruments material level is consistently incorrect by the same amount?
    • J
      Julia SloanAug 17, 2025
      If the material level displayed on your Pulsar Measuring Instruments is consistently incorrect by the same amount, check the empty level (P105), display offset (P802), and measurement offset (P851).
  • N
    Nathan LynnAug 22, 2025
    How to troubleshoot a blank display and non-firing transducer on Pulsar Ultra 3 Measuring Instruments?
    • G
      Gloria RamosAug 22, 2025
      If the display on your Pulsar Measuring Instruments is blank and the transducer is not firing, check the power supply, voltage selector switch, and fuse.
  • A
    Alison BarnesAug 27, 2025
    What to do if my Pulsar Ultra 3 display shows 'Xducer Flt'?
    • J
      jameshicksAug 27, 2025
      If your Pulsar Measuring Instruments display shows 'Xducer Flt', it indicates a fault with the transducer wiring. Check the wiring to the transducer.
  • J
    Jesse CunninghamSep 1, 2025
    What to do if my Pulsar Ultra 3 display shows 'No Xducer'?
    • P
      patriciajohnsonSep 1, 2025
      If your Pulsar Measuring Instruments display shows 'No Xducer', check the wiring to the transducer.

Summary

Chapter 1 Start Here

Functional Description

Details the operational principles and features of the Ultra 3.

Chapter 2 Installation

Chapter 3 How To Use Your Ultra 3

Operating the Controls

Explains how to interact with the Ultra 3's display and controls.

Chapter 4 Ultra Wizard

Ultra Wizard Menu

Introduces the wizard for configuring the Ultra 3 for specific applications.

Chapter 5 Level; Volume

Chapter 6 Pump

Quick Setup

Guides on setting up the Vantage 3 for pump control applications.

Chapter 7 Flow

Quick Setup and Application Selection

Guides on setting up the Flow 3, including quick setup and application choice.

Chapter 8 Parameter Listing and Descriptions

Application and Relay Parameters

Lists and describes parameters for application setup, relays, general control, and pumps.

System, Communication, and Testing Parameters

Covers system settings, communication interfaces, and unit testing procedures.

Chapter 9 Troubleshooting

Troubleshooting Guide

Lists common symptoms and provides suggested solutions for device issues.

Pulsar Ultra 3 Specifications

General IconGeneral
Enclosure RatingIP68
TypeUltrasonic level transmitter
Resolution1mm
Process Connection2" NPT
Output4-20 mA, HART
Battery LifeNot applicable (wired power supply)