Page 158 
P722 Cd  
Displays the calculated value for Cd when, P700 = 2 BS3680flumes. 
P723 Ce 
Displays the calculated value for Ce when, P700 = 3 BS3680 weirs. 
P724 Cu  
Displays  the  calculated  value  for  Cu  when, P700 =  2  BS3680  flume  and 
P701 = 3 or 4 U-Throated flume. 
P725 Kb 
Displays  the  calculated  value  for  Kb  when,  P700  =  3  BS3680  weirs  and 
P701 = 1 Rectangular weir. 
Breakpoints 
P730-P793 Breakpoints 
Where  the  Primary  Measuring  device  does  not  match  any  of  the  pre-
programmed  devices  contained  in  the  Ultra  3,  then  a  universal  volume 
calculation  can  be  performed.  A  head  Vs  flow  chart  is  used,  to  enter  a 
number of Breakpoints for the head and flow (P730-793), which is either 
provided  by  the  manufacturer  or  created  based  on  the  dimensions  of  the 
device. 
Breakpoints should be entered in pairs of head and the corresponding flow 
for that head. The first pair entered must be for zero head and flow and the 
last pair entered must be for maximum head and flow. The higher number 
of breakpoints (pairs) entered then the greater accuracy there will be. There 
are a maximum number of 32 breakpoints (pairs) for head and flow that can 
be entered. 
Tables 
P796 Reset Breakpoints 
This parameter allows the resetting, to the default value, of all previously set 
breakpoints (P730-793), without having to access them individually. When 
it is necessary to reset or amend particular breakpoints this can be achieved 
by  directly  accessing  the  desired  parameter  (P730-793)  and  changing  as 
required.