P214, P224, P234 - Relay Setpoint 2 
This parameter determines the “OFF” point for the general control relay  
Relay Setpoints are entered in values of Measurement Units (P104) 
 
P219, P229, P239 - Relay Max.Rate 
This parameter will allow a General Control Relay to be switched at a pre-
determined Rate of change of Level, irrespective of the “ON” level setpoint 
P213, 223, 233. Once a General Control relay has been switched “ON” by 
the pre-determined Rate of Change, it will remain energised until the level 
reaches the “OFF” level setpoint P214, 224, 234.  
Max. Rate is entered in Measurement Units (P104) per minute and can be 
entered  as  either  positive  (increasing  level)  or  negative  (decreasing level) 
values. 
Pumps 
When Ultra Wizard = 2 Pump or 3 Flow  
P210, 220, 230 = 2 (Pump) 
When a relay  is  being  used  for  a  pump  function, the second parameter 
determines  the  pump  duty  that  will  be  used  to  determine  the  operating 
cycle.  
P211, P221, P231 - Relay Function, 
This  parameter defines  which  pump duty  the  relay  should  respond  to  as 
follows. 
All pumps are used to assist each other 
(run at the same time) and each pump 
has its own setpoints. (P213, 223, 233 & 
P214, 224, 234). 
If a pump fails to meet the demand (due 
to malfunction, intake blockage etc.), 
then it is stopped and another pump shall 
take over. Each pump has its own 
setpoints. (P213, 223, 233 & P214, 224, 
234).