Page 164 
Bargraph 
When Ultra Wizard = 3 Flow 
P829 Bargraph  
By  default,  the  bar  graph  will  be  representative  of,  as  a  percentage,  the 
reading  obtained,  as  determined  by  the  Mode  P100.  This  parameter  is 
automatically  set  to  the  correct  default  option  when  selecting  the  Mode 
P100, but can be changed if required. The options are as follows: 
Bargraph will be representative of level. 
Bargraph will be representative of head. 
Bargraph will be representative of flow. 
 
mA Output Parameters 
Range 
P830 mA Range 
This parameter determines the range of the mA output, from the following. 
mA  output  directly  proportional  to  the  mA  mode 
(P831), so if the reading is 0% the output is 0 mA. If 
the reading is 100% the output is 20 mA. 
mA  output  directly  proportional  to  the  mA  mode 
(P831), so if the reading is 0% the output is 4 mA. If 
the reading is 100% the output is 20 mA. 
mA  output  inversely  proportional  to  the  mA  mode 
(P831), so if the reading is 0% the output is 20 mA. If 
the reading is 100% the output is 0 mA. 
mA  output  inversely  proportional  to  the  mA  mode 
(P831), so if the reading is 0% the output is 20 mA. If 
the reading is 100% the output is 4 mA.