23 / 31
3.5.3 System turns on
Warning: Double check all the power cables and communication cables. Make sure the voltage
of the inverter is same level with the battery system before connection. Check all the power
switch of every battery system is OFF.
System turns on step:
1) Check all cables are connected rightly. Check grounding is connected.
2) Open protect cover of breaker and turn on Power Switch first then turn on BMS Switch.
If DC side has voltage higher than 48V, then BMS will wake up by inverter.
If DC side do not have voltage, then press start button for more than 5 seconds, and then
wait.
It takes 10-30 seconds for BMS self-checking and wake up battery modules. Then the system is
ready. You can touch the LED button and see how led flash.
Caution: When the breaker is tripped off because of over current or short circuit, please wait
30min before turns on again, otherwise may cause the breaker damage.

Other manuals for Pylontech Force-L2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pylontech Force-L2 and is the answer not in the manual?

Pylontech Force-L2 Specifications

General IconGeneral
Battery TypeLithium Iron Phosphate (LiFePO4)
Nominal Voltage51.2 V
Capacity per Module3.55 kWh
Usable Energy3.2 kWh
Operating Temperature-10°C to 50°C
Communication InterfaceCAN, RS485
Warranty10 years
Peak Discharge Current (3 sec)100 A
Protection DegreeIP20
Cycle Life6000 cycles at 80% DoD