Matrix 424, 832, 832+ Installation Manual
Page 50 RINS918-6
5. SAFETY & APPROVALS
SAFETY
1. A technically competent person must carry out the mains installation in accordance with the national and
local electrical installation regulations
2. Protective Earth: This equipment must be earthed/grounded.
3. Functional Earth: Must be connected to earth terminal to allow the equipment to operate correctly. Has
no safety implications.
4. Connect the unit to a single pole, unswitched, 3 Amp fused spur, using 0.75mm
2
cable. If the Neutral
cannot be positively identified use a double pole disconnect version.
5. Always remove / isolate the mains supply before carrying out any servicing of the panel.
6. Fuses: For continued protection against the risk of fire, replace only with the same type and rating of
fuse.
7. There are no user serviceable parts inside the equipment.
8. This unit should be mounted so that there will be no outside access to the electrical cable entry point.
9. Ventilation: To ensure the correct airflow, always mount the unit vertically with the unit having a clear
space on all sides. It must not be covered by clothes, furnishings, boxes, etc. It must not be mounted
close to, or above, heat radiating sources.
10. On completion of wiring, use tie-wraps to prevent any loose wires causing a safety hazard.
11. The mechanical mounting of the unit must be secure enough to carry the full weight of the unit including
all batteries.
12. Batteries: Ensure that the battery terminal connections will not create an electrical short-circuit on the
case metalwork when the unit is closed. Use insulated battery lead connectors.
13. Dispose of old batteries as required by environmental legislation / recommendations.
14. The battery case must have a flame-retardant rating of UL94-V2/V1/V0 – IEC60950:2000
15. Water: The equipment must be kept free from dampness, water and any other liquids. It is only suitable
for installation indoors.
Protective Earth Must be connected to the electrical installation earth / ground
Protective Bonding Must be connected to the equipment protective earth terminal
Functional Earth
Must be connected to earth terminal to allow the equipment to
operate correctly. Has no safety implications.
Read Read equipment instructions
Anti-Static precautions are required.

Table of Contents

Other manuals for Pyronix Matrix 832

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pyronix Matrix 832 and is the answer not in the manual?

Pyronix Matrix 832 Specifications

General IconGeneral
BrandPyronix
ModelMatrix 832
CategoryControl Panel
LanguageEnglish

Related product manuals