Installation, Operation and Technical Manual Rectifier Technologies
158-1872-01 56 19-Feb-14
Modem enable; this can be toggled between ON and OFF.
When a change is made, the front panel is disabled while
the modem is activated/deactivated.
Modem
On
The screens below (up to Note) will only be displayed if the
modem is enabled (ON)
Modem
Off
When modem communication is selected CSU checks once
a minute if the modem is set to Auto Answer. If Auto Answer
was disabled (i.e. loss of power to the modem) CSU will re-
initialise the modem.
This and next screen may not be seen on some models.
Two characters Country Code is required when Integrated
Modem Interface is installed. See Remote Communication
Interfaces section of this manual for listing of country codes.
Country Code
09
The default setting for this parameter is no country code”.
To disable existing code put a space (blank) in place of any
of the characters and press ENTER.
Country Code
None
This and next screen may not be seen on some models.
Some models of external modems may require an
additional initialisation string. The string can be up to 10
characters long - initial ‘AT’ command is not required.
Cust Init String
&B1L3
The default setting for this parameter is “no custom string”.
To disable existing initialisation string put a space (blank) in
place of the first character and press ENTER.
Cust Init String
None
Phone 1; number tried first when an alarm occurs.
Numbers up to 20 digits long can be stored. If the number
is longer than 10 digits, it is displayed in two screens.
Phone 1
0398887788
Example of second screen for continuation of phone
number
Phone 1 Cont
2323
Phone 2; this number will be tried if the first number does
not respond. This menu item is followed by Phone 2 Cont”
(as for Phone 1).
Phone 2
0398880033
Phone 3; this number will be tried if the second number
does not respond. This menu item is followed by Phone 3
Cont” (as for Phone 1).
Phone 3
0398880033
Note: To have Alarm Report and/or Daily Report sent to local PC, switch the Reports ON, and Modem Off
Audio Alarm Enable; can be toggled from On through
Timeout to Off; when On, the audible alarm will sound when
any alarm occurs. The sound can be silenced by pressing
the ENTER button while viewing Home screen.
Audio Alarm
On
Audio Alarm will sound for two minutes (if not acknowledged
earlier).
Audio Alarm
Timeout