SETPOINT VALUE
Enter the desired setpoint value. Setpoint values can also be entered in the
Quick Programming Mode when the setpoint is configured as &(% in Module 3.
(See Module 2 for Exchange Parameter Lists explanation.)
0 to ;;;;;
6.4 MODULE 6 - Setpoint (Alarm) Parameters (
>3$,%
)
PARAMETER MENU
Module 6 is the programming for the setpoint (alarms) output parameters. To
have setpoint outputs, a setpoint Plug-in card needs to be installed into the
PAXR (see Ordering Information). Depending on the card installed, there will
be two or four setpoint outputs available. This section replaces the bulletin
which comes with the setpoint plug-in card. Please discard the separate
literature when using the Plug-in card with the PAXR. For maximum input
frequency, unused Setpoints should be configured for *44 action.
The setpoint action determines certain setpoint feature availability. The chart
below illustrates this.
PARAMETER DESCRIPTION
SETPOINT ACTION
BOUNDARY
)*7(+
LATCH
#:%5"
LIt-n
Annunciators Yes Yes Yes
OUt-n
Output Logic Yes Yes Yes
SUP-n
Power Up State Yes Yes Yes
SP-n
Setpoint Value Yes Yes Yes
trC-n
Setpoint Tracking Yes Yes Yes
tyP-n
Boundary Type Yes Yes Yes
Stb-n
Standby Operation Yes Yes Yes
HyS-n
Setpoint Hysteresis No Yes No
tOFF-n
Setpoint Off Delay No Yes No
tON-n
Setpoint On Delay Yes Yes Yes
tOUt-n
Setpoint Time Out Yes No No
TIMED OUT
%*7%
SETPOINT PARAMETER AVAILABILITY
!
"
(*
$,$&#
SETPOINT SELECT
Select a setpoint (alarm output) to open the remaining module menu. (The
“n” in the following parameters will reflect the chosen setpoint number.) After
the chosen setpoint is programmed, the display will default to $,$&# (*. Select
the next setpoint to be programmed and continue the sequence for each setpoint.
Pressing PAR at $,$&# (* will exit Module 6.
!
"
(*!
*7%3=
SETPOINT OUTPUT LOGIC *
Normal ((*!) turns the output “on” when activated and “off” when
deactivated. Reverse (!&?) turns the output “off” when activated and “on” when
deactivated.
!
"
*44
$7,3=
SETPOINT POWER UP STATE *
$:?& will restore the output to the same state it was at before the meter was
powered down. *( will activate the output at power up. *44 will deactivate the
output at power up.
!
"
(*!
#'%3=
SETPOINT ANNUNCIATORS*
*44
disables the display of the setpoint annunciator. Normal ((*!) displays
the corresponding setpoint annunciator of an “on” alarm output. Reverse (!&?)
displays the corresponding setpoint annunciator of an “off” alarm output. 4#:$"
flashes the corresponding setpoint annunciator of an “on” alarm output.
$,39$,38
$,32$,3/(*
*44 (*! 4#:$"!&?
(*! !&?
*($:?& *44
* Factory Setting can be used without affecting basic start-up.
!
"
%*7%
:5%3=
SETPOINT ACTION
*44 #:%5"%*7% )*7(+
tOUt
With Boundary action, the setpoint output activates when the
rate value is greater than or equal to (for
%6@ = "') or less than
or equal to (for
%6@ = #*) the setpoint value. The setpoint output
will deactivate (Auto reset) as determined by the hysteresis
value.
bOUNd
OFF
LAtCH
When not using a setpoint, it should be set to *44 (no action).
With Latch action, the setpoint output activates when the rate
value is equal to the setpoint value. The setpoint output remains
active until reset. If after reset, the rate value is greater than or
equal to (for
%6@ = "') or less than or equal to (for %6@ = #*) the
setpoint value, the output will reactivate.
With Timed Out action, the setpoint output cycles when the rate
value is greater than or equal to (for
%6@ = "') or less than or
equal to (for
%6@ = #*) the setpoint value. The Setpoint Time Out
(
%*7%3=) and Setpoint On Delay (%*(3=) values determine the
cycling times.