6.2 MODULE 3 - Display and Program Lock-out
Parameters (
83#*5
)
PARAMETER MENU
Module 3 is the programming for Display lock-out and “Full” and “Quick”
Program lock-out.
When in the Display Mode, the three displays can be read consecutively by
repeatedly pressing the DSP key. An annunciator indicates the display being
shown. These displays can be locked from being visible. It is recommended that
the display be set to #*5 when the corresponding function is not used.
“Full” Programming Mode permits all parameters to be viewed and
modified. This Programming Mode can be locked with a security code and/or
user input. When locked and the PAR key is pressed, the meter enters a Quick
Programming Mode. In this mode, setpoint values can still be read and/or
changed per the selections below.
SELECTION DESCRIPTION
!&+
Visible in Display Mode
#*5
Not visible in Display Mode
Not visible in Quick Programming Mode
#*5
&(%
!&+
DESCRIPTIONSELECTION
Visible and changeable in Quick Programming Mode
Visible but not changeable in Quick Programming Mode
RATE DISPLAY LOCK-OUT *
MAX. MIN. DISPLAY LOCK-OUT *
These displays can be programmed for #*5 or !&+.
The setpoint displays can be programmed for
#*5, !&+, or &(% (See the
following table). Accessible only with the Setpoint Plug-in card installed.
Entry of a non-zero value will cause the prompt
5*+& to appear when trying
to access the “Full” Programming Mode. Access will only be allowed after
entering a matching security code or universal code of 222. With this lock-out,
a user input would not have to be configured for Program Lock-out. However,
this lock-out is overridden by an inactive user input configured for Program
Lock-out.
SECURITY CODE *
!
"
0
5*+&
!
"
#*5
$,39
SETPOINT 1 to 4 ACCESS LOCK-OUT *
!
"
#*5
$,3/
!
"
#*5
$,32
!
"
#*5
$,38
!
"
#*5
#*
!
"
!&+
!:%&
!
"
#*5
"'
* Factory Setting can be used without affecting basic start-up.
PROGRAMMING MODE ACCESS
SECURITY
CODE
USER INPUT
CONFIGURED
USER INPUT
STATE
“FULL” PROGRAMMING MODE ACCESS
0
not ,#*5
———— “Full” Programming Immediate access.
>0
not ,#*5
———— Quick Programming After Quick Programming with correct code # at 5*+& prompt.
>0
,#*5
Active Quick Programming After Quick Programming with correct code # at 5*+& prompt.
>0
,#*5
Not Active “Full” Programming Immediate access.
0
,#*5
Active Quick Programming No access
0
,#*5
Not Active “Full” Programming Immediate access.
WHEN PAR KEY IS
PRESSED
Throughout this document, Programming Mode (without Quick in front) always refers to “Full” Programming (all meter parameters are accessible).
n = Setpoints 1 to 4