TROUBLESHOOTING
CHECK: Active (lock-out) user input
ENTER: Security code requested
PROGRAM: Module 4 as Hi-t: 0.0 LO-t: 3271.1 (to disable zero chop feature)
PRESS: Reset KEY (If cannot clear contact factory.)ERROR CODE (Err 1-4)
CHECK: Corresponding option card installationMODULES or PARAMETERS NOT ACCESSIBLE
INCREASE: Module 1 filtering, rounding, input range
CHECK: Wiring is per EMC installation guidelines
JITTERY DISPLAY
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level“ULUL” in DISPLAY (SIGNAL LOW)
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level“OLOL” in DISPLAY (SIGNAL HIGH)
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level,
Module 4 Display Offset is zero, press DSP for Input Display
PERFORM: Module 9 Calibration (If the above does not correct the problem.)
INCORRECT INPUT DISPLAY VALUE
CHECK: Module 3 programmingMAX, MIN, TOT LOCKED-OUT
PROGRAM LOCKED-OUT
CHECK: Power level, power connectionsNO DISPLAY
REMEDIESPROBLEM
DISPLAY ZERO’S AT LEVELS BELOW 1% OF RANGE
For further assistance, contact technical support at the appropriate company numbers listed.
PARAMETER VALUE CHART Programmer ________________ Date ________
PAX MODEL NUMBER ________ Meter# _____________ Security Code __________
Signal Input Parameters
PAXT: TEMPERATURE SCALE
DISPLAY PARAMETER
FACTORY
SETTING
PAXT: INPUT TYPE
MODEL DEPENDENT
* DISPLAY RESOLUTION
PAXH: INPUT COUPLE
USER SETTING
PAXT: DISPLAY OFFSET
DISPLAY ROUNDING INCREMENT
FILTER SETTING - PAXH
SCALING POINTS
PAXT: ICE POINT SLOPE
* INPUT VALUE 1
SCALING STYLE - NOT PAXT
* DISPLAY VALUE 1
* INPUT VALUE 2
* DISPLAY VALUE 2
* DISPLAY VALUE 4
* DISPLAY VALUE 5
* DISPLAY VALUE 3
* INPUT VALUE 4
* INPUT VALUE 5
* INPUT VALUE 3
* Decimal point location is model and programming dependent.
* INPUT VALUE 7
* DISPLAY VALUE 12
* INPUT VALUE 9
* DISPLAY VALUE 14
* INPUT VALUE 8
* DISPLAY VALUE 13
* INPUT VALUE 6
* DISPLAY VALUE 11
* INPUT VALUE 10
* DISPLAY VALUE 15
* DISPLAY VALUE 7
* INPUT VALUE 13
* INPUT VALUE 11
* DISPLAY VALUE 9
* DISPLAY VALUE 16
* INPUT VALUE 15
* DISPLAY VALUE 8
* INPUT VALUE 14
* DISPLAY VALUE 6
* INPUT VALUE 12
* DISPLAY VALUE 10
* INPUT VALUE 16
USER SETTING
FACTORY
SETTING
PARAMETERDISPLAY
FILTER ENABLE BAND - PAXH