MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
150 8540780 • 07/05/2018 • Rev.33
English
Response Time
The max response time of the network starting from emergency stop is given by the formula:
t
r
= [(212 ms x n°Master)-260ms]
Emergency
Stop
Pressing
MASTER n°1
MASTER n°2
MASTER n°3
MASTER n°4
t
rMASTER1
t
rMASTER2
t
rMASTER3
t
rMASTER4
12,6ms
164ms
376ms
488ms
With reference to the Figure 66 and Figure 67, when the IN input of the NETWORK function block of
one of the 4 nodes moves to condition 0 (FALSE):
1. The local OUTPUT moves to condition 0 (FALSE);
2. The RUN signal continues to be sent via the Network_out lines;
3. The states of the remaining nodes remain unchanged;
4. In that case, local reset must be used. The Reset-in LED flashes to indicate this condition. This condition is
signaled by the corresponding LED flashing Reset_In entrance.
The affected node will be restarted with its own reset.
Master M1 signals with Network operative
164

Table of Contents

Other manuals for Reer MOSAIC MI8O2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reer MOSAIC MI8O2 and is the answer not in the manual?

Reer MOSAIC MI8O2 Specifications

General IconGeneral
BrandReer
ModelMOSAIC MI8O2
CategoryController
LanguageEnglish

Related product manuals