EasyManua.ls Logo

Reer MOSAIC MI8O2 - MR2 and MR4 Module Specs; MR2;MR4 Safety Technical Data; MOR4 and MOR4 S8 Module Specs

Reer MOSAIC MI8O2
169 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
36 8540780 • 07/05/2018 • Rev.33
English
MR2 - MR4 modules
MR2 – MR4: TECHNICAL DATA CONCERNING SAFETY
FEEDBACK CONTACT PRESENT
FEEDBACK CONTACT MISSING
PFHd
SFF
MTTFd
DCavg
PFHd
SFF
MTTFd
DCavg
3,09E-10
99,6%
2335,94
98,9%
tcycle1
DC13 (2A)
9,46E-10
60%
2335,93
0
tcycle1
DC13 (2A)
8,53E-11
99,7%
24453,47
97,7%
tcycle2
1,08E-10
87%
24453,47
0
tcycle2
6,63E-11
99,8%
126678,49
92,5%
tcycle3
6,75E-11
97%
126678,5
0
tcycle3
8,23E-09
99,5%
70,99
99,0%
tcycle1
AC15 (3A)
4,60E-07
50%
70,99
0
tcycle1
AC15 (3A)
7,42E-10
99,5%
848,16
99,0%
tcycle2
4,49E-09
54%
848,15
0
tcycle2
1,07E-10
99,7%
12653,85
98,4%
tcycle3
1,61E-10
79%
12653,85
0
tcycle3
3,32E-09
99,5%
177,38
99,0%
tcycle1
AC15 (1A)
7,75E-08
51%
177,37
0
tcycle1
AC15 (1A)
3,36E-10
99,6%
2105,14
98,9%
tcycle2
1,09E-09
60%
2105,14
0
tcycle2
8,19E-11
99,7%
28549,13
97,5%
tcycle3
1,00E-10
88%
28549,13
0
tcycle3
tcycle1: 300s (1 commutation every 5 minutes)
tcycle2: 3600s (1 commutation every hour)
tcycle3: 1 commutation every day
MOR4 MOR4S8 module

Table of Contents

Other manuals for Reer MOSAIC MI8O2