— English Fillcontrol Plus — 06.07.2016 - Rev. B
Hardness reduction is calculated from the difference of the overall water hardness
GH
actual
and the target water hardness GH
target
.
• Hardness reduction = GH
actual
-GH
target
l °dH
Enter the value in the controller. Consult the
manufacturer information for third-party
Hardness reduction
10 °dH (033)
The attainable soft water capacity is calculated from the type of softening used and the
specified hardness reduction.
Fillsoft I, soft water capacity ≤ 6000/hardness red. l
Fillsoft II, soft water capacity ≤ 12000/hardness red. l
Enter the value in the controller. Consult the manufacturer information for the values of
third
-party products.
Cap. soft water
00600 l (032)
Remaining capacity, soft water.
Available soft water capacity.
Remaining cap. soft w.
000020 l (035)
Replace the softening cartridge.
Manufacturer specification for the replacement interval (in months) of the softening
cartridges.
The controller displays "Softening" upon expiry of this time.
Replacement in
18 months (034)
Recommended maintenance messages.
Next maintenance
Without maintenance recommendation.
– 060: Maintenance recommendation in months. 012 months
For the output of messages to the floating contact,
see chapter 9.3 "Messages" on page 35 .
Select one of the following options:
Floating fault contact
Output of all messages.
Output of all messages identified with "xxx" ("01", for example).
Switch to the "Fault memory" sub
-menu.
Press "OK" to open the menu.
Use the "▼▲" buttons to open the sub-menu.
Fault memory˃
The last 20 alarms are stored with fault type, date, time, and fault code.
See the chapter "Messages" for more
information about the ER... messages.
ER 01…xx 05