37
ER Code
Alarm
Group
message
Causes
Remedy
Alarm reset
32 Undervoltage YES Supply voltage too low. Check power supply.
33
Adjustment parameter
faulty
EPROM parameter memory
defective.
Inform Reflex Customer Service.
34
Main board
communication faulty
Connecting cable
defective.
Main board defective.
Inform Reflex Customer Service.
35
Digital input voltage
faulty
Short-circuit of input
voltage.
Check the wiring at the digital
inputs (water meter, for example).
36
Analogue input voltage
faulty
Short-circuit of input
voltage.
Check the wiring at the analogue
inputs (pressure/level).