Troubleshooting54
Error List
REFUsol 100K
982059/02
2020-11
9002F
FFS is read-only The internal data storage is not possible due to
a flash error.
Please contact REFU Service.
90030
DC share too high The measured DC-Part in AC current exceed
the defined limit.
90031
ETH link lost The Ethernet connection was interrupted.
Check all Ethernet cables in the system (on
the inverter, router, switch, etc.) for correct
connection and damage.
90032
Restart A notice that the system is restarted.
If these instructions occur more frequently
in daily operation, please contact REFU
Service.
90034
DC share too high The measured DC component in the AC cur-
rent is above the configured limit value. The
device restarts automatically.
Please contact REFU Service.
90050
AC condition The AC switch-on condition has not yet been
fulfilled (mains frequency, AC voltage).
Wait until the network is stable.
90051
DC condition The DC switch-on condition not yet fulfilled
(DC voltage).
Wait until the DC voltage is sufficient.
90052
User lock active The user lock is active.
Deactivate the user lock by pressing the
"Clear" (REFUsol 100K) key for at least 5 s.
90054
Overvoltage 2 The mean grid voltage is above the configured
limit value of the voltage mean value monitor-
ing.
Measure the voltage of all three phases
with REFUset and a True RMS meter.
Check the configured voltage average and
the configured nominal voltage.