Troubleshooting 55
Error List
REFUsol 100K
982059/02
2020-11
EnglishDeutsch
90055
Grid overvoltage The phase phase voltage exceeds the config-
ured limit value for the configured duration.
Measure the voltage of all three phases
with REFUset and a True-RMS meter.
Check the configured voltage limit and the
configured nominal voltage.
90056
Grid undervoltage The phase phase voltage falls below the con-
figured limit value for the configured duration.
90057
Watchdog C0 The internal firmware protection function has
been triggered.
Please contact REFU Service.
90058
Watchdog C1
90059
LT Firmware The LT/safety processor firmware is defective.
Download the correct firmware package
again from the manufacturer's website and
restart the update.
If the error persists, please contact REFU
Service.
90061
Update fault No action necessary.
90062
Fault ride through Indication of instabilities in the network, which
must be passed through according to different
country regulations.
90071
DFLASH Fixed
90072
DFLASH Reset The device has lost important configuration
parameters.
Please contact REFU Service.
90073
Test Info No action necessary.
90074
Test Noti
90075
Test Temp Noti