Troubleshooting56
Error List
REFUsol 100K
982059/02
2020-11
90082
HW VPos feeding The hardware protection has detected an im-
permissible overvoltage in the positive DC link.
Check DC voltage for permissible range.
90083
HW VNeg feeding The hardware protection has detected an im-
permissible overvoltage in the negative DC
link.
90084
HW PowNok feeding The hardware protection has detected a prob-
lem in the power supply of the switches.
Open and close the DC switch.
If error occurs more than once, contact
REFU Service.
90085
HW DcUnsy feeding The hardware protection has detected an im-
permissible asymmetry in the DC link.
90086
HW driver feeding The hardware protection has detected a prob-
lem in the circuit breaker driver.
90087
HW overcurrent L1 The hardware protection has detected an im-
permissible overcurrent in L1, L2, or L3.
90088
HW overcurrent L2
90089
HW overcurrent L3
9008A
IGBT overtemperature The temperature of the IGBT's exceeds the
permissible limit value.
Do not run the inverter at full load at high
ambient temperatures.
9008B
Air overtemperature The temperature of the interior exceeds the
permissible limit value.