Troubleshooting 59
Error List
REFUsol 100K
982059/02
2020-11
EnglishDeutsch
900A3
SafetyRelay 1 broken The safety relay L1 is jammed.
Please contact REFU Service.
900A4
SafetyRelay 2 broken The safety relay L2 is jammed.
900A5
SafetyRelay 3 broken The safety relay L3 is jammed.
900A6
MainRelay 1 broken The safety relay L1 is jammed.
900A7
MainRelay 2 broken The safety relay L2 is jammed.
900A8
MainRelay 3 broken The safety relay L3 is jammed.
900AA
External FAN NOK The external fans do not work. The device au-
tomatically limits its power to keep the tem-
perature of the device within a safe range.
Replace the external fans according to the
manual.
900AB
Internal FAN NOK The internal fan does not work. The device au-
tomatically limits its power to keep the tem-
perature of the device within a safe range.
Please contact REFU Service.
900AC
Systemstart info No action necessary.
A017D
Phase defect The actual current value deviates from the set
current value.
Please contact REFU Service.
A017E
HW error activation General hardware shutdown by the inverter
during the activation phase. This error should
be corrected automatically.
If error occurs more than once, contact
REFU Service.