Troubleshooting60
Error List
REFUsol 100K
982059/02
2020-11
A017F
HW VPos activation The hardware protection has detected an im-
permissible overvoltage in the positive DC link
during the activation phase.
Check DC voltage for permissible range.
A0180
HW VNeg activation The hardware protection has detected an im-
permissible overvoltage in the negative DC
link during the activation phase.
A0181
HW PowNok activation The hardware protection has detected a prob-
lem with the circuit-breakers during the acti-
vation phase.
If error occurs more than once, contact
REFU Service.
A0182
HW DcUnsy activation The hardware protection has detected an im-
permissible asymmetry in the DC link during
the activation phase.
Open and close the DC switch.
If this error occurs more than once, contact
REFU Service.
A0183
HW driver activation The hardware protection has detected a prob-
lem in the circuit breaker driver during the ac-
tivation phase.
A0184
HW I L1 activation The hardware protection has detected an im-
permissible overcurrent in L1 during the acti-
vation phase.
A0185
HW I L2 activation The hardware protection has detected an im-
permissible overcurrent in L2 during the acti-
vation phase.
A0186
HW I L3 activation The hardware protection has detected an im-
permissible overcurrent in L3 during the acti-
vation phase.