Troubleshooting 61
Error List
REFUsol 100K
982059/02
2020-11
EnglishDeutsch
A0187
HW error PreActiv The hardware protection has detected a gen-
eral error before the activation phase.
If error occurs more than once, contact
REFU Service.
A0188
HW VPos PreActiv The hardware protection has detected an im-
permissible overvoltage in the positive DC link
before the activation phase.
Check DC voltage for permissible range.
A0189
HW VNeg PreActiv The hardware protection has detected an im-
permissible overvoltage in the negative DC
link before the activation phase.
A018A
HW PowNok PreActiv The hardware protection has detected a prob-
lem with the circuit-breakers before the acti-
vation phase.
If error occurs more than once, contact
REFU Service.
A018B
HW DcUnsy PreActiv The hardware protection has detected an im-
permissible asymmetry in the DC link before
the activation phase.
Open and close the DC switch.
If this error occurs more than once, contact
REFU Service.
A018C
HW driver PreActiv The hardware protection has detected a prob-
lem in the circuit breaker driver before the ac-
tivation phase.
Error Code Message Description Instructions