94
4x0260 Exhaust fan 0 - x sec Differential - Unsigned Word
4x0261 Humidification (divider 100) Gain - Signed Word
4x0262 Humidification 0 - x sec Integral - Unsigned Word
4x0263 Humidification 0 - x sec Differential - Unsigned Word
4x0264
4x0265
4x0266
4x0267 Dehumidification (divider 100) Gain - Signed Word
4x0268 Dehumidification 0 - x sec Integral - Unsigned Word
4x0269 Dehumidification 0 - x sec Differential - Unsigned Word
4x0270 Air quality (factor 100) Gain - Signed Word
4x0271 Air quality 0 - x sec Integral - Unsigned Word
4x0272 Air quality 0 - x sec Differential - Unsigned Word
4x0273 Casc controller tmp (factor 10) Gain - Signed Word
4x0274 Casc controller tmp 0 - x sec Integral - Unsigned Word
4x0275 Humidity cascade control (Factor 10) Gain - Signed Word
4x0276 Humidity cascade control 0 - x sec Integral - Unsigned Word
4x0277 HeatPumpHtg (factor 100) Gain - Signed Word
4x0278 HeatPumpHtg 0 - x sec Integral - Unsigned Word
4x0279 HeatPumpHtg 0 - x sec Differential - Unsigned Word
4x0280 HeatPumpClg (factor 100) Gain - Signed Word
4x0281 HeatPumpClg 0 - x sec Integral - Unsigned Word
4x0282 HeatPumpClg 0 - x sec Differential - Unsigned Word
4x0283 ElPreHtg (factor 100) Gain - Signed Word
4x0284 ElPreHtg 0 - x sec Integral - Unsigned Word
4x0285 ElPreHtg 0 - x sec Differential - Unsigned Word
4x0283 WtrPreHtg (factor 100) Gain - Signed Word
4x0284 WtrPreHtg 0 - x sec Integral - Unsigned Word
4x0285 WtrPreHtg 0 - x sec Differential - Unsigned Word
Holding register (Read/Write) [03:H] (pokračování)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks