EasyManuals Logo

Remak VCS User Manual

Remak VCS
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
9
Control units VCS
Control and Protection Functions
Wiring
n A shielded conductor must be used for the Modbus bus
connection.  e maximum conductor length depends on
the communication speed. A maximum length of approx.
1000 m is recommended for the baud rate of 9600 Bd.  e
recommended conductors are included in the documentation
created by the AeroCAD design program.
n e controller is connected to two terminals marked A+
and B- and to the REF signal detection reference voltage
terminal, which must always be interconnected with other
participants on the bus.
n To ensure correct functioning of the bus, the fi rst and last
device on the bus must be fi tted with a terminal resistor.  e
rst device, i.e. the master controller, terminal resistor setting
is performed using the so ware (ensured by REMAK in the
factory).  e last device terminal resistor setting is performed
on the last frequency inverter in the line connection. Refer to
the Modbus bus wiring diagram.  e setting procedure of
the last terminal resistor is described in the documentation
for a corresponding frequency inverter. A 120 Ohm resistor
connected between the communication can also be used to
terminate the wiring.
Fan Failure Detection
n To detect any fan failure, the motor thermo-contact and
diff erential pressure sensor are connected to the frequency
inverter inputs.  e information provided by these elements
is transmitted through the Modbus communication line to the
control system, where it is processed.
Modbus RTU Communication Settings
n Each frequency inverter connected to the bus must be
assigned a unique address as defi ned in the control system
data points.
Pre-set Frequency Inverter Addresses – ModBus:
Inlet Fan
Inlet fan address =1
Backup or twin fan address =2
Backup twin fan 1 address =3
Backup twin fan 2 address =4
Outlet fan
Outlet fan address =5
Backup or twin fan address =6
Backup twin fan 1 address =7
Backup twin fan 2 address =8
Figure 10 – Inverter connection to the Modbus RTU
Figure 11 – Inverter association with a corresponding
section
terminal
resistor
RS485
FM1
Master
controller
FM2 FM3
Warning
e frequency inverter association cannot be exchanged
between diff erent sections! For information about frequency
inverter association with a corresponding section, refer to
the fi gure.
Auxiliary Fan
Auxiliary fan address =9
Twin fan address =10
Rotary Heat Regenerator
RHR motor address =11
n e data points of all frequency inverters for communica-
tion with the Modbus bus must be set in accordance with the
VCS control unit:
•  Baud rate (9600 Bd – pre-set)
• Parity (none – pre-set)
• Number of stop bits (2 stop bits – pre-set)
• Response time limit
• Number of data bits (as standard, 8 bits – pre-set)
All data points for the used frequency inverters are available
on our website: www.remak.eu
Corresponding
section number
Order
number
5
0064 / 5
00
00
64 / 5
64 / 5
64 / 5
64 / 5
0064 / 500
0064 / 5
00
64 / 5
0064 / 500
64 / 5
64 / 5
64 / 5
64 / 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Remak VCS and is the answer not in the manual?

Remak VCS Specifications

General IconGeneral
BrandRemak
ModelVCS
CategoryControl Unit
LanguageEnglish