EasyManua.ls Logo

REVCON RHF-Active - RHF-Active; RHF-Hybrid

Default Icon
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4. Product-Overview
User manual RHF-Active 16
4.2.1 RHF-Active
Non-linear Loads (e.g. frequency converter) load the mains with distorted (non-sinewave)
currents. Such currents increase losses in wires and transformers and cause distorted voltage,
which stress all connected loads in multiple manners (e.g. resulting in reduced lifetime). RHF-
Active measure the distorted currents and generate for each harmonic up 60th a phase shifted
compensation current. The sum of distorted load current and compensation current results in a
(nearly) sinewave grid current. The required nominal current of the RHF-Active depends on the
nominal current of the load and its distortion. If the distorting load is a frequency converter, the
percentage of compensation current is ca. 25-30%. This results in a grid current with mitigated
distortion of ca. 5%.
4.2.2 RHF-Hybrid
Especially for high loads (>>100kW) quite high level of compensation current is required. To
keep this level low, the RHF-HybridSystem may be used. This system consists out of RHF-
Active added by one or two RHF-Passive. The RHF-Active controls usage of passive filter
circuits, resulting in several important advantages:
Only ca. 10% of the nominal current are left for active compensation.
The resulting distortion of the grid current may go down to less than 1% (THDi <1%).
The total costs are significantly lower than by using exclusively active filters.