5. Installation instructions
User manual RHF-Active 34
5.3.9 EPO and RHF-Active ID
Terminal label Function
GND_O
EPO connection for usage as part of EMERGENCY OFF line. If
the contact to be wired here is closed, the EMERGENCY OFF
function is active.
EPO
ID_DS Reserved for future purpose
A new RHF-Active will be supplied with a short circuit wire at the EPO connector. This is
mandatory to ensure that the RHF-Active will NOT start at first powering up.If the RHF-Active
has not been powered up for >4 month, wait 1 hour before starting it (RUN). To start the RHF-
Active, switch off the supply voltage, disconnect the EPO connector (or remove the wire) and
power it up again. The error will be cleared automatically and the product can be used.
Stop!
If RHF-Active is started (RUN) not observing this instruction, the product may be
damaged severely.
STOP